| Mode |
LI1K/LI1KS |
LI2K/LI2KS |
LI3k/LI3KS |
LI5K/LI5KS |
| Capacity |
1kva / 0.7Kw |
2Kva / 1.4Kw |
3KVA/2100w |
5KVA/3.5Kw |
| Input |
Nominal Voltage |
220VAC / 110V |
| Input Range |
160 - 286V or 87 - 152VAC |
| Frequency |
50Hz± 3Hz |
| Output |
Voltage |
220 or 110V ±2%(battery mode) |
| Transfer time |
≤4ms |
| Frequency |
50HZ ± 0.3Hz( (Battery mode) |
| Waveform |
Sine Wave (Battery mode) |
| Battery |
Type |
Maintenance free valve regulated lead acid (VRLA) battery |
| DC Voltage |
24v |
48v |
48v |
48VDC |
| Standard Type |
12v/12ah*2 |
12v/17ah*4 |
12v/17ah*4 |
12V/24AH*4 |
| Long time type |
External battery |
| Standard discharge time Full load |
8-9minutes |
20~25minutes |
12~15minutes |
12~15minutes |
| Long time type |
Decided by battery number |
| Standard discharge time Half load |
18minutes |
40~50minutes |
24~30minutes |
24~30minutes |
| Long time type |
Decided by battery number |
| Standard Charge Current |
1-2A |
Max 3.5 |
| Long time type charge current |
Max 12A |
| Recharge time |
3~8hours |
12hours |
12hours |
12hours |
| Recharge time |
Decided by battery number |
| Protection |
Overload, short -circuit, battery voltage,over and low voltage, over temperature |
| Communication interface |
RS232/DRY CONTACT With monitoring software |
| Thunder protection |
IEEE C62.41 CATEGORY A Standard |
| Dimension |
216*170*439 |
432*196*546 |
432*196*546 |
196*432*546 |
| Standard type Net weight |
18.5Kg |
46.8Kg |
50.3Kg |
91.8Kg |
| Long time type Net weight |
15.5Kg |
32Kg |
38Kg |
71Kg |
| REMARK |
LI*K -Standard Type , LI*KS-Long Time type. LI5K have one Battery Pack |
| |