Servo Stabilizer (Air-cooled)
 
 
  SERVO CONTROLLED VOLTAGE STABILIZERS ARE AVAILABLE IN FOUR MODELS
 
PS analog meter
 
DPM digital meter
DPS digital control
DCM DC motor control for high speed of correction
   

CAPACITIES :

1) 0.5 KVA to 40 KVA I PH

 

2) 1.5 KVA to 200 KVA 3 PH

 

 

SPECIFICATIONS :

 

Input Voltage Range

300 V – 460 V AC 50 Hz 3 PH

Other Input Ranges

245 V- 460 V AC 3Ph

340 V- 460 V AC 3Ph

360 V- 460 V AC 3Ph

other ranges as per customer requirement

Output Voltage

380 V / 400 V/ 415 V AC 3Ph 50 Hz

System

Unbalanced 4 Wire : R Y B N

Connections

Star

   
 

Operating Frequency

47 Hz to 53 Hz

Output Voltage Adjustable

380 V to 415 V AC in 3Ph

220 V to 240 V AC in 1Ph

Output Voltage Regulation

± 1%

Over Load Capacity

120%

Correction Rate

15 V / 20 V / 35 V / Sec-1Ph

25 V / 35 V / 60 V / Sec-3Ph

110V/Sec for D.C. Motor controlled

Waveform Distortion

Nil

Output Waveform

True Reproduction of Input

Insulation

Class 'B'

Short CKT Period & percentage

300 % for 250 m.sec.

Normal Operating Temperature

0ºC to 45ºC

Climatic Conditions

90 % RH.Max.Non-Condensing at 35º C

Mode  of System

Fully Automatic / Manual

System Construction

AS PER IS : 9815 of 1994

STANDARD PROTECTIONS
 
Low voltage protection
High Voltage protection
Overload Protected with MCB / MCCB
Single Phasing Preventer
 
 
 
PANEL INDICATIONS
 
Input     - ON
Output  - ON
Input     - Low
Input     - High
Output  - Cut-off
 
 
 
  PANEL METERS
 
Volt Meter With Selector Switch to read Input / Output Voltages, phase to phase and phase to neutral.
Ammeter With Selector Switch (From 15 KVA 3Ph onwards )
 
 OPTIONAL ACCESSORIES IN 3 Ph SYSTEM
 
INPUT UNDER / OVER VOLTAGE TRIP
OUTPUT UNDER / OVER VOLTAGE ALARM
DIGITAL VOLTMETER / AMMETER
FREQUENCY METER (Digital / Analog)
FREQUENCY TRIP HIGH / LOW ADJUSTABLE (With setting thumb Wheel switch)
MCB/MCCB FOR OUTPUT
Dimmer Protection Arrangement
Phase Reversal Protection
 
  SAILENT FEATURES
 

Quick Response

Quickest response time 10 ms.(half a cycle)

High Overload capacity

Higher overload capabilities for high starting    and   regenerative    currents repeated frequency    in CNC   Machines.

Fast Correction

Fastest rate of correction up to 70 V/sec.

No Hunting, No Oscillations,
No Noise Generation

Machine – Wound Variable Auto Transformer,   with   special    Carbon Brush to minimize carbon   deposit    and for smooth commutation.

 
  ENERGY SAVINGS
 
Better efficiency of 98% achieved by use of prime grade Lamination.
Electrolytic copper wires of 99.99% purity.
Special designed transformers to minimize losses.
Special sensing circuit to ensure constant Output Voltage even with distorted input from D.G. set. Conforms to stringent  Defense  specifications. Tropicalised design
 
 
                                                                       Copyright 2007 Zodiac UPS All rights reserved